Wholesale Marketplace
Home >

Recycling Valve Regulated Lead Acid Battery 12V 75AH For UPS / EPS System

Categories Valve Regulated Lead Acid Battery
Brand Name: CGB
Model Number: EV12750
Certification: CE/UL/TLC/ISO
Place of Origin: Wuhan, China
MOQ: 50 pcs
Price: Negotiation
Payment Terms: T/T or L/C
Supply Ability: 21600pcs Per Month
Delivery Time: 30 days
Packaging Details: Packed in carton, and then reinforced with pallet or wooden case for outer packing
Product Name: EV12750
Application: UPS, EPS,Telecommunication
Voltage: 12V
Capacity: 75AH
Size Of Battery: 259*168*208*227mm
Terminal: FP-16,FP-17/FP-24/RT-07
Weight: 25.85KG
Case: ABS-HB, V0
  • Product Details
  • Company Profile

Recycling Valve Regulated Lead Acid Battery 12V 75AH For UPS / EPS System

Recycling Valve Regulated Lead Acid Battery 12V 75AH For UPS / EPS System

Specifications:

Nominal Voltage12V
Nominal Capacity (C20)75Ah (10.5V,at 25℃)
DimensionLength259mm
Width168mm
Height208mm
Total Height227mm
WeightApprox25.85kg
TerminalFP-16,FP-17/FP-24/RT-07
Internal ResistanceApprox.7.5mΩ (25℃)
Max Charging Current22.5A

























FEATURES:
* Extra Long Life: our batteries are designed with high quality grid alloy enables the grid with features of anti-corrosion, low gas emission and excellent deep cycle performance, as well as high density and special deep cycle lead paste prescription is adopted to ensure extra long cycle life.

* High Reliability and Safety: High strength ABS battery container and lid, perfect safety valve design, and high strength & excellent large current electroconductivity copper terminal design are adopted to ensure the batteries with high reliability and safety at extreme condition.

* High Environmental Adaptability: our batteries adopts special fumed silica Gel in electrolyte and special Gel type separator to prevent electrolyte sratification. This can significantly improve the battery's service life and environmental adptability.

* Non-Cadmium Design, Environment-friendly: our batteries have adopted internationally leading technology - container formation non-cadmium production technology, which is in the leading position in the industry. It helps to save energy 28.5%, save water 90%, and non-discharge of waste water.



Applications:

● UPS & EPS system

● Telecommunication

● Banks & Financial Centre
. High Power Backup Supply

● Emergency Power Systerm

● Alarm & Security system

STORAGE
● Batteries should be stored in dry and clean warehouse which has good air exchange system. Batteries should avoid direct sunlight. Batteries should not be near to heat (such as radiator, the distance should more than1m). Batteries should avoid any toxic gas and organic solvent.
● When the ambient temperature is less than 25℃, the longest storage life is 6 months. If ambient temperature is higher, the longest storage life varies as specified in below chart.

Storage Temperature (℃)≤2526~3334~40
Storage Time (Month)631





● Batteries should be recharged within the storage life or before using.
Charging methods: maximum charging current 8A, constant voltage 2.45±0.05V/cell (25℃);
Charging time: 15~20h; Temperature compensation coefficient: -5mV/℃/cell.

OPERATION

Equalizing Charge
1 Equalizing Charging Occasion

It is unnecessary to equalizing charge the battery in normal operation. But if the float voltage is set too low, or it is affected by environment temperature so that the consistency of batteries in battery group is very bad, then equalizing charge should be adopted when the following conditions happen:

  1. After 3 months’ float charging operation and the there are more than 2 pieces batteries which voltage is less than 13.08V;
  2. The voltage difference of each battery reaches +/-0.48V in float charging operation; the voltage difference of each battery reaches +/-0.30V after 12 months float charging 12 months.

2 Equalizing Charging Methods
Using limiting current (0.30C20 (A)) and constant voltage charging.

Charging Voltage(V/piece)Time of Charging(h)
Working Environment Temperature13-20℃Working Environment Temperature21-32℃
14.04824
14.42412



Cycle Operation
Cycle operation means to charge and discharge battery periodically.
1 Discharge Current and Final Voltage
Discharge current bigger, final voltage lower. Below table shows the final voltage at the difference discharge current:

Charging Current(A)Final Voltage(V/piece)
0.1C2010.5
0.5C2010.2
3C209.6

2 Charging Current, Charging Voltage and Charging Time
Battery should be charged with limiting current and constant voltage when cycle charging. Setting a limiting current at 0.30C20 (A) and a limiting voltage, start charging with original current till the battery terminal voltage reaches the definite voltage and time. The set of float charging voltage is relevant with the temperature of the battery. When the temperature is between 21-26℃, the floating voltage is 13.65V/pcs. Adjust the floating voltage(-18.0V/℃/piece) when the temperature is above the range. If the ripple current of the charging equipment is accord with the recommendation of the Manual, use the daytime temperate as the floating charging temperature, otherwise use terminal temperature. The best floating voltage of the battery in different working environment temperature is suggested as following:

Working Environment Temperature (℃)Charging Voltage(V/pcs)Charging Time(h)
-5~414.824
5~1014.724
11~1514.620
16~2014.520
21~2614.420
27~3214.316
33~3814.216
39~4414.116
45~5014.016

























































































Quality Recycling Valve Regulated Lead Acid Battery 12V 75AH For UPS / EPS System for sale